A.V.S 3 Phases SH3-500K/3II 500kVA (500,000VA), Input 260V–430V, Output 380V
- Input Voltage: 260V – 430V (150V ~ 248V)
- Output Voltage: 380V ± 2~3%
- Power Rating: 500kVA
- Dimensions (L x W x H): (1750 x 850 x 1430) x 3 mm
- Weight: 1750 kg
Description
TECHNICAL SPECIFICATIONS
-
Input Voltage: 260V – 430V (150V ~ 248V)
-
Output Voltage: 380V ± 2~3%
-
Power Rating: 500kVA
-
Frequency: 49 – 62Hz
-
Response Time: 1 – 3 seconds
-
Operating Ambient Temperature: -5°C to +40°C
-
Control Principle: DC Servo Motor Control
-
Insulation Resistance: Greater than 3MΩ at DC 500V
-
Dielectric Strength: 1500V tested for 1 minute [1500V/1min]
-
Dimensions (L x W x H): (1750 x 850 x 1430) x 3 mm
-
Weight: 1750 kg
OUTSTANDING FEATURES
-
Operates based on servo motor regulation, ensuring continuous and stable voltage output.
-
Integrated with three protection functions: overload protection, input overvoltage protection, and automatic power cutoff.
-
Independent three-phase adjustment, suitable for harsh power grids and unbalanced phase voltage conditions.
-
Quiet operation with low self-power consumption, allowing electrical equipment to run at full designed capacity, improving durability and saving energy.
-
Industrial design structure, meeting the demand of high-power electrical equipment.
-
Suitable for standard power grid conditions with input voltage range from 260V to 430V per phase.
-
Protects equipment from damage caused by overvoltage, undervoltage, or unstable power supply, enhancing equipment lifespan and maximizing energy efficiency.